Biogas Equipment Inspection Checklist

Digester gas is flammable, can displace air and can contain toxic components. This checklist covers a routine walk-around, how to work out how long the gas holder buffers a stopped engine, and what to log.

Why it matters

Small leaks, stuck relief devices and failed sensors cause most surprises on a digester. A written round makes problems visible early and helps contractors diagnose them. Operate within the manufacturer manual, your permits and trained staff limits, and never enter a tank, vessel or gas pipe space.

Step by step

  1. Make a numbered list of inspection points: cover, gas piping, condensate traps, relief devices, flare, sensors, pumps, mixers, electrical and ventilation.
  2. Walk the same route on a set schedule with a gas detector as the manual directs, and stop work and leave if it alarms.
  3. Check piping, valves and fittings for corrosion, damage and leaks using the method the manufacturer allows, such as soapy water on small joints, and never a flame.
  4. Confirm flare, pressure relief and emergency shutdown devices are free of ice, nests and debris, and have them function-tested by those qualified to do so.
  5. Read the gas holder level and production meter, record both, and work out hours of storage so you know how long a stopped engine leaves.
  6. Tag any failed item with a date and name, restrict access to the area, and call a qualified technician rather than repairing gas parts yourself.

Worked example

Illustrative: Gas production is 2,400 cubic feet per day, or 2,400 / 24 = 100 cubic feet per hour. A holder with 10,000 cubic feet of usable storage buffers 10,000 / 100 = 100 hours, about 4 days, before gas must be flared. A round of 14 inspection points weekly is 14 x 52 = 728 checks a year; if 3 points fail, 3 / 14 = 21 percent need work.

Printable worksheet: biogas equipment inspection

  • Inspector, date and detector tested (yes or no): ____________
  • Points inspected ______ ; points failed ______ ; failed share = ______ percent
  • Gas production ______ cu ft/day / 24 = ______ cu ft/hour
  • Holder storage ______ cu ft / hourly production = ______ hours
  • Flare and relief devices tested on (date): ______
  • Failed item, tag number and who was called: ____________
  • Area restricted until (date): ______

Common mistakes

  • Testing for leaks with a flame or a spark-making tool instead of the method named in the manual.
  • Letting the holder fill past its marked level because production looked steady last week.
  • Treating a recurring detector alarm as a nuisance and silencing it rather than finding the source.
  • Letting an untrained employee tighten gas fittings or open pressure parts without a technician.

Frequently asked questions

Who can repair gas piping?

Trained, qualified technicians following the manufacturer procedure and local code. Staff can inspect, log and report. Ask your digester vendor, your insurer and your state agency what qualifications are expected for service on your system.

How often should I inspect?

A daily visual and a fuller weekly or monthly round are common, but the manufacturer manual and your permit set the schedule. Follow those, and add extra checks after storms, shutdowns or repairs.

Is biogas safe in a barn?

Gas can collect in low or closed spaces, so equipment and plans must keep it out of occupied buildings. Check the design with the vendor and local code, and keep detectors working where the plan calls for them.

Official sources

Educational only. Permit, setback and application rules vary by state; confirm with your state agency, NRCS and a certified planner. State dairy waste resources.